Error and Notification Messages
www.lsi.com/channel/products 293
However, if the temperature is very cold, condensation can occur and cause
media errors and damage. Take steps to bring the operating environment back
within the enclosure manufacturer’s specifications.
Allow cold equipment to warm up gradually before powering on.
8024 Enclosure temp above operating
Event Type
Error.
Cause
Applies to 9750 and 9690SA controllers.
The enclosure temperature is above the enclosure manufacturer’s specified
operating temperature.
Action
Make sure that the fans are operational. Check for blocked ventilation in the
enclosure and the operating environment.
Continued operation of the enclosure at high temperatures may lead to data
loss and operational failure.
8025 Enclosure temp removed
Event Type
Warning.
Cause
Applies to 9750 and 9690SA controllers.
The temperature sensor in the enclosure has been removed or has failed and
the enclosure temperature is no longer being monitored.
Action
The temperature sensor should be replaced or repaired. This may require
specialized skills. Contact your enclosure manufacturer for more information.